ZN63-12(VS1-12)indoor high voltage vacuum circuit breaker for switchgear 12kV
-
ZN63-12(VS1-12)indoor high voltage vacuum circuit breaker for switchgear 12kV
This technical specification stipulate the requirement of ZN63-12(VS1-12)/T1250-31.5 model indoor AC HV vacuum circuit breaker in use condition, technical parameter, design structure, test method, test rule, packing, transportation, and storage etc.
This technical specification is applicable for ZN63-12(VS1-12)/T1250-31.5 model indoor AC HV vacuum circuit breaker. This VCB can be used in indoor site with three phases, 50Hz, rated voltage 12KV. It mainly serves in mineral enterprise, power plant and substation for control and protection of electric equipment. It can be installed both in trolley type switchgear and fixed type switchgear. This VCB has merits of long life, easy maintenance, no pollution, no explosion, low noise etc, and it is fit for use in stringent work condition with frequent operation etc.Main technical data
ITEM UNIT DATA Rated voltage kV 12 Rated current A 1250 Rated frequency Hz 50 Rated insulation level Lightning impulse withstand voltage Phase to phase, phase to earth kV 75 Insulating distance of contact 85 1min power frequency withstand voltage Phase to phase, phase to earth 42 Insulating distance of contact 49 4s rated short time withstand current kA 31.5 Rated short circuit break current 31.5 Rated peak value withstand current 80 Rated short circuit making current 80 Rated operation sequence O-0.3s-CO-180s-CO Break times of rated short circuit current Times 50 Mechanical life 20000 Break current of rated different phases earth fault kA 27.4 Break current of rated single capacitor bank A 400 Break current of rated back to back capacitor bank 400 Rated open operation voltage/current V/A DC(AC)220/1.1 DC(AC)110/2.2 Rated making operation voltage/current DC(AC)220/1.1 DC(AC)110/2.2 Release work current of rated transient over current A 5 Rated circuit of secondary circuit V DC(AC)220 DC(AC)110 Rated voltage of energy storage motor DC(AC)220 DC(AC)110 Rated output power of energy storage motor W 50 Energy storage time s ≤10 1min power frequency withstand voltage of secondary circuit V 2000 Insulating distance of contact mm 11±1 Overtravel of contact 3+1 0 Center distance between different poles 210±1 Allow abrasion thick of contact 3 Average opening speed m/s 1.2±0.2 Average closing speed 0.7±0.2 Contact closing jump time ms ≤2 Close/open synchronized of three phases ≤2 Main circuit resistance μΩ ≤55 Opening time ms 25~60 Closing time 35~75 Operation characteristic of operation mechanism 65%~120% rated voltage Reliable open/close ≤30% rated voltage Can not open -
ZN63-12(VS1-12)indoor high voltage vacuum circuit breaker for switchgear 12kV
-
ZN63-12(VS1-12)indoor high voltage vacuum circuit breaker for switchgear 12kV
About us
We are specialty on providing medium voltage and high voltage circuit breaker and switchgear components, such as 12KV, 24 KV, 36KV and 40.5KV embedded cylinder,insulated operating rod,auxiliary circuit socket,counter,circuit breaker board,vacuum circuit breaker plastic panel,connection terminal,vacuum circuit breaker and so on.These components apply on 630A, 1250A, 2500A, 3150A and 4000A VS1 (ZN85-40.5) circuit breaker and KYN28A-12 and KYN61 high voltage switchgear.
Our Advantages1. Strict quality control and excellent after-sales service.
2. Experienced staffs answer all of your question in fluent English.
3. Customized design is available. OME&ODM are welcomed.
4. Exclusive and unique solution can be provided to our customer by our well-trained and professional engineers and staffs.
If you would like a quotation or further information on this product, please fill in the form below and we will reply to you within 1 working day.